NICE RBA3R10 control unit wiring
Which types of cable to use for each component in an operator setup with a NICE RBA3R10 control unit are listed in the following “shopping” list:
Minimum required:
- Power supply – 3×1.5 mm2. If the power cable is longer than 30 m, use a larger one, for example 3 x 2,5 mm2
Optional accessories:
- Photoelectric cells:
- transmitter TX: 2×0,5 mm2
- receiver RX: 2×0,5 mm2
- Flashing light:
- for the light: 2×1 mm2
- for the antenna: shielded coaxial cable with an impedance of 50 Ohm (type RG58)
- Alternatively, use a two-core cable (2x0,5 mm2) if you want to open it using, for example, a standard switch.
- Any other BlueBus accessory: 2×0,5 mm2. If the BlueBus cable is longer than 20m, use 2×1 mm2